27™ (TT) Series
ClimateMaster: Smart. Responsible. Comfortable.
Electrical Data
All TT Units with ECM Fan Motor TT Units (ECM) Standard TT Units (ECM) with ClimaDry
Model
Compressor
HWG
Pump
FLA
Ext
Loop
Pump
FLA
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amps
Max
Fuse/
HACR
(2)
Supply Wire (2)
ClimaDry
Pump
FLA
Total
Unit
FLA
Min
Circuit
Amps
Max/
Fuse
HACR
(2)
Supply Wire (2)
RLA LRA Qty
Min
AWG
60°C
(1, 4)
Max
Length Ft
(m) (3)
Min
AWG
60°C
(1, 4)
Max
Length Ft
(m) (3)
026 10.3 52.0 1 0.40 4.0 4.3 19.0 21.6 30 10 86 (26.2) 0.8 19.8 22.4 30 10 82 (25.2)
038 16.7 82.0 1 0.40 4.0 4.3 25.4 29.6 45 10 63 (19.1) 0.8 26.2 30.4 45 8 97 (29.6)
049 21.2 96.0 1 0.40 4.0 7.0 32.6 37.9 50 8 78 (23.8) 1.07 33.7 39.0 60 8 76 (23.1)
064 25.6 118.0 1 0.40 4.0 7.0 37.0 43.4 60 6 108 (32.9) 1.07 38.1 44.5 70 6 105 (32.1)
072 27.2 150.0 1 0.40 4.0 7.0 38.6 45.4 70 6 103 (31.4) 1.07 39.6 46.4 70 6 101 (30.8)
Rated Voltage of 208-230/60/1 Min/Max Voltage of 197/254
HACR circuit breaker in USA only All fuses Class RK-5
Notes:
(1) If wire is applied at ambient greater than 86°F (30°C), consult table 310-16 of the National Electrical Code (NEC). The ampacity of non-metallic
sheathed cable (NM), otherwise known as Romex cable, shall be that of 60°C (140°F) conditions per the NEC Article 336-26. If other wiring is used,
consult applicable tables of the NEC.
(2) Current carrying capacity (amperes) of the wire used must not be less than the fuse/breaker size used.
(3) Wire length based on one way measurement with 2% voltage drop.
(4) Wire size based on 60°C copper conductor and Minimum Circuit Ampacity.